Danfoss VLT Flow Drive FC 111 Programming Manual page 113

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
Define how many info/data frames the device is allowed to send while holding the token.
Table 205: Range:
Min: 1
8-74 "I am" Service
Default value: [0] Send at power-up
Conversion index: -
Table 206: Option:
[0]
Send at power-up
Select when the device should send the I am service message only at power-up.
[1]
Continuously
Select when the device should send the I am service message continuously with an interval of approxi-
mately 1 minute.
8-75 Intialisation Password
Default value: admin
Conversion index: 0
Enter the password needed for execution of Drive Re-initialization from BACnet.
Table 207: Range:
Min: 1
8-79 Protocol Firmware version
Default value: 0
Conversion index: -2
Firmware revision of the drive is in index 0, Modbus is in index 1, Metasys N2 is in index 2, FLN is in index 3, BACnet is in index 4.
Table 208: Range:
Min: 0
4.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus communication via the FC port.
8-80 Bus Message Count
Default value: 0
Conversion index: 0
This parameter shows the number of valid telegrams detected on the bus.
Table 209: Range:
Min: 0
Max: 4294967295
8-81 Bus Error Count
Default value: 0
Conversion index: 0
This parameter shows the number of telegrams with faults (for example, CRC fault), detected on the bus.
Danfoss A/S © 2021.07
Max: 65534
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: VisibleString
Max: 1
Parameter type: Range
Data type: u_int16
Max: 655
Parameter type: Range
Data type: u_int32
Parameter type: Range
Data type: u_int32
Default value: 1
2-setup: 1 setup
Change during operation: True
Default value: admin
2-setup: 1 setup
Change during operation: False
Default value: 0
2-setup: 1 setup
Change during operation: True
Default value: 0
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982 | 113
Parameters

Advertisement

Table of Contents
loading

Table of Contents