14-21 Automatic Restart Time
Default value: 10 s
Conversion index: 0
To start the automatic reset function, enter the time interval from trip. This parameter is active when parameter 14-20 Reset Mode is
set to [1] - [13] Automatic reset.
A value of 0 s cannot be set when parameter 14-20 Reset Mode is set to option [13] Infinite auto reset.
Table 243: Range:
Min: 0 s
14-22 Operation Mode
Default value: [0] Normal operation
Conversion index: -
To reset all parameter values to default, select [2] Initialisation.
Table 244: Option:
[0]
Normal op-
Select [0] Normal operation for normal operation of the drive with the motor in the selected application.
eration
[2]
Initialisation
Select [2] Initialisation to reset all parameter values to default settings, excluding bus communication param-
eters, parameter group 15-0* Operating Data, and parameter group 15-3* Alarm Log. The drive is reset during
the next power-up. Parameter 14-22 Operation Mode also reverts to the default setting [0] Normal operation.
14-23 Typecode Setting
Default value: 0
Conversion index: 0
Service use only.
Table 245: Range:
Min: 0
14-27 Action At Inverter Fault
Default value: [1] Warning
Conversion index: -
Select how the drive acts in the case of overvoltage, overcurrent, short circuit, or grounding errors.
Table 246: Option:
[0]
Trip
[1]
Warning
Danfoss A/S © 2021.07
Select [13] Infinite Automatic Reset for continuous resetting after tripping.
Parameter type: Range
Data type: u_int16
N O T I C E
Max: 600 s
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int8
Max: 255
Parameter type: Option
Data type: u_int8
Disable the protection filters and trip at the 1st fault.
Run the protection filters normally.
2-setup: All setups
Change during operation: True
Default value: 10 s
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: False
Default value: 0
2-setup: All setups
Change during operation: True
AU363928304090en-000101 / 130R0982 | 133