Danfoss VLT Flow Drive FC 111 Programming Manual page 16

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
Parameter
Option
Parameter 3-41
0.01–3600.00 s
Ramp 1 Ramp
Up Time
Parameter 3-42
0.01–3600.00 s
Ramp 1 Ramp
Down Time
0.0–400.0 Hz
Parameter 4-12
Motor Speed
Low Limit [Hz]
Parameter 4-14
0.0–400.0 Hz
Motor Speed
High Limit [Hz]
0.0–400.0 Hz
Parameter 4-19
Max Output
Frequency
Parameter 5-40
See parameter 5-40 Function
Function Relay
Relay.
Parameter 5-40
See parameter 5-40 Function
Function Relay
Relay.
0.00–10.00 V
Parameter 6-10
Terminal 53
Low Voltage
Parameter 6-11
0.00–10.00 V
Terminal 53
High Voltage
0.00–20.00 mA
Parameter 6-12
Terminal 53
Low Current
Parameter 6-13
0.00–20.00 mA
Terminal 53
High Current
Parameter 6-19
[0] Current
Terminal 53
[1] Voltage
mode
Parameter
[0] Off
30-22 Locked
[1] On
Rotor Detection
Parameter
0.05–1 s
30-23 Locked
Rotor Detection
Time [s]
16 | Danfoss A/S © 2021.07
Default
Usage
Size related
If induction motor is selected, the ramp-up time is from 0 to
rated parameter 1-23 Motor Frequency. If PM motor is selec-
ted, the ramp-up time is from 0 to parameter 1-25 Motor
Nominal Speed.
Size related
For induction motors, the ramp-down time is from rated pa-
rameter 1-23 Motor Frequency to 0. For PM motors, the ramp-
down time is from parameter 1-25 Motor Nominal Speed to 0.
Enter the minimum limit for low speed.
0 Hz
100 Hz
Enter the maximum limit for high speed.
100 Hz
Enter the maximum output frequency value. If parameter
4-19 Max Output Frequency is set lower than parameter 4-14
Motor Speed High Limit [Hz], parameter 4-14 Motor Speed High
Limit [Hz] is set equal to parameter 4-19 Max Output Frequen-
cy automatically.
Select the function to control output relay 1.
[9] Alarm
Select the function to control output relay 2.
[5] Drive run-
ning
Enter the voltage that corresponds to the low reference val-
0.07 V
ue.
10 V
Enter the voltage that corresponds to the high reference val-
ue.
Enter the current that corresponds to the low reference val-
4 mA
ue.
20 mA
Enter the current that corresponds to the high reference val-
ue.
Select if terminal 53 is used for current or voltage input.
[1] Voltage
[0] Off
0.10 s
Programming
AU363928304090en-000101 / 130R0982