Danfoss VLT Flow Drive FC 111 Programming Manual page 74

Hide thumbs Also See for VLT Flow Drive FC 111:
Table of Contents

Advertisement

VLT® Flow Drive FC 111
Programming Guide
[53]
Hand start
A signal applied puts the drive into hand-on mode as if [Hand On] is pressed and a normal stop com-
mand is overridden. If the signal is disconnected, the motor stops. To make any other start commands
valid, assign another digital input to Auto Start and apply a signal. The [Hand On] and [Auto On] keys
have no impact. The [Off] key overrides Hand Start and Auto Start. Press either [Hand On] or [Auto On]
to reactivate Hand Start and Auto Start. If there is no signal on Hand Start or Auto Start, the motor stops
regardless of any normal start command applied. If a signal is applied to both Hand Start and Auto
Start, the function is Auto Start.
[54]
Auto start
A signal applied puts the drive into auto-on mode as if [Auto On] is pressed. See also [53] Hand Start.
[60]
Counter A (up)
Input for increment counting in the SLC counter.
[61]
Counter A
Input for decrement counting in the SLC counter.
(down)
[62]
Reset Counter
Input for reset of counter A.
A
[63]
Counter B (up)
Input for increment counting in the SLC counter.
[64]
Counter B
Input for decrement counting in the SLC counter.
(down)
[65]
Reset Counter B
Input for reset of counter B.
[101]
Sleep
A signal applied puts the drive into sleep mode.
[120]
Lead Pump
A signal applied puts the lead pump into start mode.
Start
[121]
Lead Pump Al-
A signal applied puts the lead pump into alternation mode.
ternation
[130]
Pump 1 Inter-
A signal applied puts pump 1 into interlock mode.
lock
[131]
Pump 2 Inter-
A signal applied puts pump 2 into interlock mode.
lock
[132]
Pump 3 Inter-
A signal applied puts pump 3 into interlock mode.
lock
[133]
Pump 4 Inter-
A signal applied puts pump 4 into interlock mode.
lock
[134]
Pump 5 Inter-
A signal applied puts pump 5 into interlock mode.
lock
[190]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 0
[191]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 1
[192]
Fire Mode Ref
Enable a selection of 1 of the 8 fire mode references according to
Bit 2
74 | Danfoss A/S © 2021.07
If no run permissive signal is applied but either run, jog, or freeze commands is activated, the status
line in the display shows either Run Requested, Jog Requested, or Freeze Requested.
N O T I C E
Table
Table
Table
AU363928304090en-000101 / 130R0982
Parameters
133.