4.3.2 1-1* Motor Selection
Parameter group for setting general motor data. This parameter group cannot be adjusted while the motor is running.
1-10 Motor Construction
Default value: [0] Asynchron
Conversion index: -
Select the motor design type.
Table 41: Option:
[0]
Asynchron
For induction motors.
[1]
PM, non salient
For permanent magnet (PM) motors with surface-mounted (non-salient) magnets. Refer to parameter
SPM
1-14 Damping Gain to parameter 1-17 Voltage filter time const. for details about optimizing the motor
operation.
[3]
PM, salient IPM
For permanent magnet (PM) motors with interior (salient) magnets, with inductance saturation control.
The following parameters are active ('x') depending on the setting of parameter 1-10 Motor Construction.
Table 42: Active Parameters
Parameter 1-10 Motor Construction
Parameter 1-00 Configuration Mode
Parameter 1-03 Torque Characteristics
Parameter 1-06 Clockwise Direction
Parameter 1-08 Motor Control Bandwidth
Parameter 1-14 Damping Gain
Parameter 1-15 Low Speed Filter Time Const.
Parameter 1-16 High Speed Filter Time Const.
Parameter 1-17 Voltage filter time const.
Parameter 1-20 Motor Power [kW]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 1-26 Motor Cont. Rated Torque
Parameter 1-29 Automatic Motor Adaption (AMA)
Parameter 1-30 Stator Resistance (Rs)
Parameter 1-33 Stator Leakage Reactance (X1)
42 | Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
[0] Asynchron
x
x
x
x
x
x
x
x
x
x
x
x
2-setup: All setups
Change during operation: False
[1] PM, non salient SPM
[3] PM, salient IPM
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AU363928304090en-000101 / 130R0982