Programming Guide
Table 151: Range:
Min: 1 s
6-01 Live Zero Timeout Function
Default value: [0] Off
Conversion index: -
Select the timeout function. The function set in parameter 6-01 Live Zero Timeout Function is activated if the input signal on terminal
53 or 54 is below 50% of the value in parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal 53 Low Current, parameter 6-20
Terminal 54 Low Voltage, or parameter 6-22 Terminal 54 Low Current for a time period defined in parameter 6-00 Live Zero Timeout
Time.
Table 152: Option:
[0]
[1]
[2]
[3]
[4]
[5]
6-02 Fire Mode Live Zero Timeout Function
Default value: [0] Off
Conversion index: -
Select the timeout function when the fire mode is active. The function set in this parameter is activated if the input signal on analog
inputs is below 50% of the low value for a time period defined in parameter 6-00 Live Zero Timeout Time.
Table 153: Option:
[0]
[1]
[2]
[3]
[4]
4.8.2 6-1* Analog Input 53
Parameters for configuring the scaling and limits for analog input 53 (terminal 53).
6-10 Terminal 53 Low Voltage
Default value: 0.07 V
Conversion index: -2
Enter the voltage (V) that corresponds to parameter 6-14 Terminal 53 Low Ref./Feedb. Value. To activate parameter 6-01 Live Zero Time-
out Function, set the value to >1 V.
Table 154: Range:
Min: 0 V
92 | Danfoss A/S © 2021.07
Max: 99 s
Parameter type: Option
Data type: u_int8
Off
Freeze output
Stop
Jogging
Max. speed
Stop and trip
Parameter type: Option
Data type: u_int8
Off
Freeze output
Stop
Jogging
Max. speed
Parameter type: Range
Data type: u_int16
Max: 10 V
Default value: 10 s
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
Default value: 0.07 V
Parameters
AU363928304090en-000101 / 130R0982