VLT® Flow Drive FC 111
Programming Guide
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
8-33 Parity / Stop Bits
Default value: [0] Even parity, 1 stop bit
Conversion index: -
Parity and stop bits for the protocol using the FC port. For some of the protocols, not all options are available. Default value refers to
the FC protocol. Changing the protocol in parameter 8-30 Protocol may change the baud rate.
Table 190: Option:
[0]
Even parity, 1 stop bit
[1]
Odd parity, 1 stop bit
[2]
No parity, 1 stop bit
[3]
No parity, 2 stop bits
8-35 Minimum Response Delay
Default value: Configuration dependent
Conversion index: -3
Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem
turnaround delays.
Table 191: Range:
Min: 0.0010 s
8-36 Maximum Response Delay
Default value: Configuration dependent
Conversion index: -3
Specify the maximum allowed delay time between receiving a request and transmitting the response. If this time is exceeded, no
response is returned.
Table 192: Range:
Min: 0.1 s
Max: 10.0 s
8-37 Maximum Inter-char delay
Default value: Configuration dependent
Conversion index: -3
Specify the maximum delay time between 2 characters in a message. Exceeding this delay time causes the message to be discarded.
Table 193: Range:
Min: 0.005 s
Max: 0.025 s
4.9.3 8-4* FC MC Protocol Set
This parameter group is for PCD write and read configurations.
106 | Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int16
Max: 0.5 s
Default value: Configuration dependent
Parameter type: Range
Data type: u_int16
Default value: Configuration dependent
Parameter type: Range
Data type: u_int16
Default value: Configuration dependent
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
AU363928304090en-000101 / 130R0982
Parameters