Table 15: Option:
[0]
Resume
Resumes operation of the drive, maintaining the same local reference and the same start/stop condition (ap-
plied by [Hand On]/[Off] on the LCP or local start via a digital input) as before the drive was powered down.
[1]
Forced
Uses saved reference [1] to stop the drive, but at the same time retains the local speed reference in memory
stop,
before powering down. After mains voltage is reconnected, and after receiving a start command (pressing
ref=old
[Hand On] key or using the local start command via a digital input), the drive restarts and operates at the re-
tained speed reference.
0-06 GridType
Default value: [Configuration dependent]
Conversion index: -
Select the grid type of the supply voltage/frequency.
Not all options are supported in all power sizes.
IT Grid is a supply mains, where there are no connections to ground.
Delta is a supply mains where the secondary part of the transformer is delta connected and 1 phase is connected to ground.
Table 16: Option:
[10]
[11]
[12]
[20]
[21]
[22]
[110]
[111]
[112]
[120]
[121]
[122]
0-07 Auto DC Braking
Default value: [1] On
Conversion index: -
Protective function against over voltage at coast in IT grid environment. This parameter is active only when [1] On is selected in this
parameter, and IT-grid options are selected in parameter 0-06 GridType.
Table 17: Option:
[0]
Off
[1]
On
Danfoss A/S © 2021.07
Parameter type: Option
Data type: u_int8
N O T I C E
380-440V/50Hz/IT-grid
380-440V/50Hz/Delta
380-440V/50Hz
440-480V/50Hz/IT-grid
440-480V/50Hz/Delta
440-480V/50Hz
380-440V/60Hz/IT-grid
380-440V/60Hz/Delta
380-440V/60Hz
440-480V/60Hz/IT-grid
440-480V/60Hz/Delta
440-480V/60Hz
Parameter type: Option
Data type: u_int8
This function is not active.
This function is active.
2-setup: 1 setup
Change during operation: False
2-setup: 1 setup
Change during operation: False
AU363928304090en-000101 / 130R0982 | 33