Examples Of Calculating The Measured Values From The Process Values - WAGO 750-494 Series Manual

3-phase power measurement module
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
5.6
Examples of Calculating the Measured Values from
the process values
The format of the measured values with sign (Int16) is the two's complement.
Generally, use the following equation to calculate the measured values from the
process values:
The scaling factors are defined in section „Collections of Measured values".
Following examples of calculating:
Voltage
Process value
Scaling factor PI
Equation
Measured value
Frequency
Process value
Scaling factor PI
Equation
Measured value
phi
Process value
Scaling factor PI
Equation
Measured value
cos phi
Process value
Scaling factor PI
Equation
Measured value
Manual
Version 1.2.0
Measured value = Process value x Scaling factor PI
1A-varints
0x000007D0 (2000)
0.01V
Measured value = Process value x Scaling factor PI
20.00 V
1A-varints
0x0000C3B8 (50104)
0.001Hz
Measured value = Process value x Scaling factor PI
50.10 Hz
1A-varints
0x 00004E3 (1251)
0.01 °
Measured value = Process value x Scaling factor PI
12.51 °
1A-varints
0x FFFFFFB2 (-78)
0.01
Measured value = Process value x Scaling factor PI
-0.78
Process Image
5A-variants
0x00003D76 (15734)
0.01V
157.34 V
5A-variants
0x0000EB9C (60316)
0.001Hz
60.32 Hz
5A-variants
0x0000226E (8814)
0.01 °
88.14 °
5A-variants
0x00000059 (89)
0.01
0.89
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-494/025-001750-494/025-000750-494/000-001