Eci Telecom NPT-1020 Installation And Maintenance Manual page 153

Table of Contents

Advertisement

NPT-1020 Installation and Maintenance Manual
Symptom
Indicators on MXC panel
FAIL
ACT
MJR
Blink
Blink
Blink
Blink
Blink
Blink
ECI Telecom Ltd. Proprietary
Probable cause
MNR
Blink
FPGA file on MXC
downloaded
unsuccessfully
Off
NPT-1020 initializes
unsuccessfully
Corrective actions
Power off and wait a few minutes before
powering on again.
When the ACT indicator is off and the MNR
indicator flashes after power-on, download
the embedded software package using the
Boot Configuration Tool.
After the embedded software package is
completely downloaded to the card, power
off and then power on the card again. The
ACT indicator should flash and the FAIL
indicator should be off after power-on if
the problem is due to a damaged software
bank.
If the FAIL indicator remains on, replace the
NPT-1020 unit.
Power off and wait a few minutes before
powering on again.
Wait a minute at most. The ACT indicator
should flash and the FAIL indicator should
be off. If not, replace the NPT-1020 unit.