WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching
from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical
connections thoroughly before making any setting changes to o2-01 and b1-07.
b1-07.
o2-01
b1-07
0
0
1
0
1
1
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator can still be used to stop drive operation when the drive is being
controlled from a remote source (i.e., not from digital operator).
No.
o2-02
STOP Key Function Selection
Setting 0: Disabled
Setting 1: Enabled
The STOP key can be used to terminate drive operation, even if the Run command source is not assigned to the digital
operator. If the drive is stopped by pressing the STOP key, the Run command must be re-input to restart the drive.
o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as user-set default values using parameter o2-
03. Once this has been done, the "Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User
Initialize". Choosing A1-03 = "1110: User Initialize" will reset all parameters to the values saved as user-set defaults.
Refer to
A1-03: Initialize Parameters on page 89
No.
o2-03
User Parameter Default Value
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for User Initialize. Once o2-03 is set to 1 and the ENTER key
is pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for "User Initialize" are cleared. Once o2-03 is set to 2 and the ENTER key is pressed, the values are
erased and the display returns to 0.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Table 2.26 LO/RE Key and b1-07
Switch from LOCAL to REMOTE
Not possible
Not possible
Will not run until a new Run command is
entered.
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Name
0 or 1
for details on drive initialization.
Name
0 to 2
2.10 o: Operator Related Settings
Table 2.26
lists the setting combinations for o2-01 and
Switch from REMOTE to LOCAL
Not possible
Not possible
Run not possible
Run not possible
Setting Range
Setting Range
Default
1
Default
0
223