1.3 Parameter Table
H2-
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-set Speed Agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active Closed: A command has been entered to clear a fault via the contact input terminals
12
Timer Output
52
H2 Contact Output Settings
All Modes
Closed: A Run command is active or voltage is output.
All Modes
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
All Modes
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
All Modes
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
All Modes
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
All Modes
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
All Modes
Closed: Power up is complete and the drive is ready to accept a Run command.
All Modes
Closed: DC bus voltage is below the Uv trip level set in L2-05.
All Modes
Closed: Drive has entered the baseblock state (no output voltage).
All Modes
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-
15).
Closed: Digital operator supplies the frequency reference.
All Modes
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
All Modes
Closed: An overtorque or undertorque situation has been detected.
All Modes
Closed: Analog frequency reference has been lost.
All Modes
Closed: Fault occurred.
All Modes
Set this value when using the terminal in the pass-through mode.
All Modes
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
expected life span.
All Modes
or from the serial network.
All Modes
Closed: Timer output.
Description
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
common_
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Reference
page
177
178
178
178
180
180
180
181
181
181
181
181
181
181
182
182
182
182