YASKAWA FSDrive-MV1000 Parameter Manual page 226

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.10 o: Operator Related Settings
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
No.
o4-02
Cumulative Operation Time Selection
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless of whether the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Run command is active (even if the motor is
not rotating) and when there is voltage output.
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-
these monitors.
No.
o4-11
U2, U3 Initialization
Setting 0: No action
The drive keeps the record already saved concerning fault trace and fault history.
Setting 1: Reset fault data
Resets the data for the U2-
ENTER key is pressed, fault data is erased and the setting of the parameter returns to 0.
o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when the power is shut off or the drive is initialized. Use o4-12 to
manually reset them.
No.
o4-12
kWh Monitor Initialization
Setting 0: No Action
The kWh data are kept as they are.
Setting 1: Reset kWh Data
Resets the kWh counter. The monitors U4-10 and U4-11 will display "0" after they are initialized. Once o4-12 is set to 1
and the ENTER key is pressed, kWh data is erased and the display returns to 0.
o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Use o4-13
to reset U4-02.
No.
Number of Run Commands Counter
o4-13
Setting 0: No Action
The Run command data are kept as they are.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed,
the counter value is erased and the setting of the parameter returns to 0.
226
Name
0 or 1
Name
0 or 1
(Fault Trace) and U3-
Name
0 or 1
Name
0 or 1
Initialization
Setting Range
and U3-
). Initializing the drive using A1-03 does not reset
Setting Range
(Fault History) monitors. Once o4-11 is set to 1 and the
Setting Range
Setting Range
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
0
Default
0
Default
0
Default
0