YASKAWA FSDrive-MV1000 Parameter Manual page 55

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
H3-11
Analog Input 2
(419H)
Gain
H3-12
(41AH)
Analog Input 2 Bias Sets the amount of bias for the function assigned for analog input 2 in %
H3-13
Analog Input Filter
(41BH)
Time Constant
Analog Input
H3-14
Terminal Enable
(41CH)
Selection
H3-16
Analog input 1
(2F0H)
offset
H3-17
Analog input 2
(2F1H)
offset
H3-
Function
Setting
0
Frequency Bias
1
Frequency Gain
Auxiliary Frequency
2
Reference (used as a Multi-
Step Speed 2)
Auxiliary Frequency
3
Reference (3rd step analog)
4
Output Voltage Bias
5
Accel/decel time gain
6
DC Injection Braking Current
Overtorque/Undertorque
7
Detection Level
Stall Prevention Level During
8
Run
Output Frequency Lower
9
Limit Level
B
PID Feedback
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
All Modes
Sets the reference value for the function assigned for analog input 2 in %
units when 10 V is input.
All Modes
units when 0 V is input.
All Modes
Sets a primary delay filter time constant for analog inputs 1 and 2. Used
for noise filtering.
All Modes
Sets of the analog input terminals to be enabled when the analog input is
set for "PID target value" (H3-
1: Analog input 1 only
2: Analog input 2 only
3: Analog inputs 1 and 2 only
All Modes
Adds an offset when the analog signal to analog input 1 is at 0 V.
All Modes
Adds an offset when the analog signal to analog input 2 is at 0 V.
H3 Analog Input Settings
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of
-100 to 0%.
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
10 V = E1-04 (maximum output frequency)
V/f
OLV
10 V = E1-05 (motor rated voltage)
All Modes
10 V = 100%
V/f
OLV
10 V = Drive rated current
All Modes
10 V = Drive rated current (V/f)
10 V = Motor rated torque (OLV, CLV)
V/f
OLV
10 V = Drive rated current
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
10 V = 100%
Description
= C).
Description
CLV
CLV
CLV
1.3 Parameter Table
Setting
Default: 100.0%
common_
Min: -999.9%
Max: 999.9%
common_
Default: 0.0%
Min: -999.9%
Max: 999.9%
common_
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
common_
Default: 3
Min: 1
Max: 3
Default: 0
common_
Min: -500
Max: 500
Default: 0
common_
Min: -500
Max: 500
common_
common_
common_
common_
common
common_
common
common_
common
common_
common_
Page
189
189
189
189
190
190
Reference
page
190
190
190
190
190
191
191
191
191
191
191
55