2.2 b: Application
b5-12: 1PID Feedback Loss Detection Selection
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No.
b5-12
Setting 0: Contact output only
A contact output set for "PID feedback low" (H2-
detection level set to b5-13 for the time set to b5-14 or longer. A contact output set for "PID feedback high" (H2-
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the times set to
b5-37. Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the
feedback value leaves the loss detection range, the output is reset.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a "FBL - Feedback
Low" alarm will be displayed and a contact output set for "PID feedback low" (H2-
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a "FBH - Feedback High" alarm
will be displayed and a contact output set for "PID feedback high" (H2-
an alarm output (H1-
range, the alarm and outputs are reset.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set in b5-14, a "FbL - Feedback Low"
fault will be displayed.
If the PID feedback value exceeds the level set to b5-36 for longer than the time set in b5-37, a "FbH - Feedback High"
fault will be displayed.
Both events trigger a fault output (H2-
Setting 3: Contact output only, even if PID is disabled by contact input
Same as b5-12 = 0. Detection is still active even if PID is disabled by a contact input (H1-
Setting 4: Feedback loss alarm, even if PID is disabled by contact input
Same as b5-12 = 1. Detection is still active even if PID is disabled by a contact input (H1-
Setting 5: Feedback loss fault, even if PID is disabled by contact input
Same as b5-12 = 2. Detection is still active even if PID is disabled by a contact input (H1-
b5-13: PID Feedback Low Detection Level
Sets the feedback level used for PID feedback low detection. The PID feedback has to fall below this level for longer
than the time b5-14 before feedback loss is detected.
No.
b5-13
116
Name
PID Feedback Loss Detection Selection
= 10). The drive will continue operation. When the feedback value leaves the loss detection
= E) and cause the drive to stop the motor.
Name
PID Feedback Loss Detection Level
Setting Range
0 to 5
= 3E) will be triggered if the PID feedback value is below the
= 3F) will be triggered. Both events trigger
Setting Range
0 to 100%
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
0
= 3E) will be triggered. If the
= 19).
= 19).
= 19).
Default
0%
=