1.3 Parameter Table

◆ F: Option Parameters

F parameters are used to program the drive for PG feedback from the motor and to function with option cards.
No.
Name
(Addr.)
Parameters F1-01 and F1-20 are used to set up a PG option card plugged into option connector CN5-C of the drive. They include "PG 1" in the
parameter name.
Parameters F1-31, F1-32, F1-35, and F1-36 are used to set up a PG option card plugged into option connector CN5-B of the drive. They
include "PG 2" in the parameter name.
Other parameters in the F1 group are used to set operation for PG options plugged into connector CN5-C and CN5-B.
F1-01
PG 1 Pulses Per
(380H)
Revolution
Operation Selection
F1-02
at PG Open Circuit
(381H)
(PGo)
F1-03
Operation Selection
(382H)
at Overspeed (oS)
F1-04
Operation Selection
(383H)
at Deviation
F1-05
PG 1 Rotation
(384H)
Selection
PG 1 Division Ratio
F1-06
for PG Pulse
(385H)
Monitor
F1-08
Overspeed (oS)
(387H)
Detection Level
Overspeed (oS)
F1-09
Detection Delay
(388H)
Time
Excessive Speed
F1-10
Deviation (dEv)
(389H)
Detection Level
Excessive Speed
F1-11
Deviation (dEv)
(38AH)
Detection Delay
Time
40
F1: PG Speed Control Card (PG-B3 / PG-X3)
V/f
OLV
Sets the number of PG (pulse generator or encoder) pulses.
Sets the number of pulses per motor revolution.
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only (Do not select this setting normally, to prevent damage to
the motor and machinery.)
4: No alarm display (Do not select this setting normally.)
Note: Due to potential damage to motor and machinery, the "Alarm only"
and "No alarm display" setting should be used only under special
circumstances.
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
V/f
OLV
0: Pulse A leads with Forward run command
1: Pulse B leads with Forward run command
V/f
OLV
Sets the division ratio for the pulse monitor used for the PG option card
installed to connector CN5-C. By setting "xyz", the division ratio becomes
= [(1 + x) / yz]. If only using the A pulse for one track input, then the input
ratio will be 1:1, regardless of what F1-06 is set to.
Setting range 1 to 132 (1 to 1/32)
V/f
OLV
Sets the overspeed detection level as a percentage of the maximum output
frequency.
V/f
OLV
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
V/f
OLV
Sets the excessive speed deviation (dEv) detection level as a percentage of
the maximum output frequency.
V/f
OLV
Sets the time in seconds for a speed deviation situation to trigger a fault
(dEv).
Description
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting
Default:
<10>
common
Min: 0 ppr
Max: 60000 ppr
common
Default: 1
Min: 0
Max: 4
common
Default: 1
Min: 0
Max: 3
common
Default: 3
Min: 0
Max: 3
Default:
<10>
common
Min: 0
Max: 1
common
Default: 1
Min: 1
Max: 132
Default: 115%
common
Min: 0%
Max: 120%
Default:
<10>
Min: 0.0 s
common
Max: 2.0 s
Default: 10%
common
Min: 0%
Max: 50%
Default: 0.5 s
common
Min: 0.0 s
Max: 10.0 s
page
158
158
158
159
159
159
158
158
159
159