B: Application - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table

◆ b: Application

Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, and a variety of other application-related settings.
No.
Name
(Addr.)
Frequency
b1-01
Reference Selection
(180H)
1
b1-02
Run Command
(181H)
Selection 1
b1-03
Stopping Method
(182H)
Selection
b1-04
Reverse Operation
(183H)
Selection
Action Selection
b1-05
below Minimum
(184H)
Output Frequency
(E-09)
b1-06
Contact Input
(185H)
Reading
b1-07
LOCAL/REMOTE
(186H)
Run Selection
Run Command
b1-08
Selection while in
(187H)
Programming Mode
Frequency
b1-15
Reference Selection
(1C4H)
2
22
b1: Operation Mode Selection
All Modes
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option board
All Modes
0: Digital operator
1: Control circuit terminal (contact input)
2: MEMOBUS/Modbus communications
3: Option board
All Modes
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
All Modes
0: Reverse enabled.
1: Reverse disabled.
V/f
OLV
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
All Modes
0: Input status is read once every millisecond and processed immediately
(for quick response)
1: Input status is read twice every millisecond and processed only if the
status is the same in both readings (robust against noisy signals)
All Modes
0: An external Run command has to be re-input at the new source to be
activated.
1: An external Run command at new source is accepted immediately.
All Modes
0: Run command not accepted while in the Programming Mode.
1: Run command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
All Modes
Enabled when an input terminal set for "External reference" (H1-
closes.
0: Digital Operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option board
Description
CLV
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting
common_
Default: 1
Min: 0
Max: 3
common_
Default: 1
Min: 0
Max: 3
common_
Default: 1
Min: 0
Max: 3
<11>
common_
Default: 1
Min: 0
Max: 1
common
Default: 0
Min: 0
Max: 3
common_
Default: 1
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 2
common_
= 2)
Default: 0
Min: 0
Max: 3
page
95
96
97
99
99
100
100
101
101

Advertisement

Table of Contents
loading

Table of Contents