2.7 H: Terminal Functions
Setting 1: Zero speed
Terminal closes whenever the output frequency or motor speed (CLV) falls below the minimum output frequency set in
E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Note: When using CLV control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the
minimum output frequency set in E1-09.
Figure 2.51
Setting 2: Speed agree 1 (f
Closes whenever the actual output frequency or motor speed (CLV) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Closed
Note: 1. Detection works in both directions, forward and reverse.
2. When using the CLV control mode, it is the motor speed ± L4-02 that is considered.
Figure 2.52
Speed agree 1
Refer to
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 204
Setting 3: User-set speed agree 1 (f
Closes whenever the actual output frequency or motor speed (CLV) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Status
The output frequency is outside the range "L4-01 ± L4-02" or outside the range "frequency reference ±L4-02".
Open
The output frequency is within the range "L4-01 ± L4-02" and also within the range "frequency reference ±L4-02".
Closed
Note: Frequency detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
178
Output frequency
or
motor speed
OFF (open)
Zero Speed
Figure 2.51 Zero-Speed Time Chart
/f
Agree 1)
ref
out
Frequency
reference
Output Frequency
or Motor Speed
OFF
Figure 2.52 Speed Agree 1 Time Chart
/f
Agree 1)
ref
set
Description
E1-09 (Minimum Output Frequency) or
b2-01 (Zero Speed Level)
ON (closed)
Description
L4-02
ON
Description
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
common_TMonly
L4-02
for more details.