Setting 7: DC bus undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A
fault in the DC bus circuit will also cause the terminal to set for "DC bus undervoltage" to close.
Status
Open
DC bus voltage is above the level set in L2-05
Closed
DC bus voltage has fallen below the trip level set in L2-05.
Setting 8: During baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Setting 9: Frequency reference source
A contact output programmed for this function shows the frequency reference source that is currently selected.
Status
Open
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15)
Closed
Frequency reference is being sourced from the digital operator.
Setting A: Run command source
A contact output programmed for this function shows the Run command source that is currently selected.
Status
Open
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed
Run command is being sourced from the digital operator.
Setting B, 17, 18, 19: Torque detection 1 (N.O., N.C.), Torque detection 2 (N.O., N.C.)
These contact output functions can be used to signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below. Refer to
page 207
for details.
Setting
Status
B
Closed
17
Open
18
Closed
19
Open
Setting C: Frequency reference loss
An output set for this function will be closed if frequency reference loss is detected. Refer to
Reference Loss Detection Selection on page 204
Setting E: Fault
The contact output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Torque detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value
set in parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value
set in parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 2 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value
set in parameter L6-05 for longer than the time specified in parameter L6-06.
Torque detection 2 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value
set in parameter L6-05 for longer than the time specified in parameter L6-06.
for details.
Description
Description
Description
Description
Description
2.7 H: Terminal Functions
L6: Torque Detection on
L4-05: Frequency
181