2.8 L: Protection Functions
L8-88: Transformer Overheat Fault (TME) Level
■
Sets the trigger temperature for the transformer overheat fault (TME) function in °C units.
Note: When the detected transformer temperature has reached the setting for this parameter, a transformer overheat fault (TME) is
detected.
No.
Name
Setting Range
Default
L8-88
Transformer Overheat Fault (TME) Level
50 to 160°C
Determined by o2-04
<1>
<1> For details on the default settings, refer to
Defaults by Drive Model Selection (o2-04) on page
82.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide