YASKAWA FSDrive-MV1000 Parameter Manual page 41

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
F1-14
PG Open-Circuit
(38DH)
Detection Time
PG Option Card
F1-20
Disconnect
(3B4H)
Detection 1
PG Card Option
F1-30
Port for Motor 2
(3AAH)
Selection
F1-31
PG 2 Pulses Per
(3B0H)
Revolution
F1-32
PG 2 Rotation
(3B1H)
Selection
F1-35
PG 2 Division Ratio
(3BEH)
for Pulse Monitor
PG Option Card
F1-36
Disconnect
(3B5H)
Detection 2
Analog Input
F2-01
Option Card
(38FH)
Operation Selection
F2-02
Analog Input
(368H)
Option Card Gain
F2-03
Analog Input
(369H)
Option Card Bias
Contact Input
F3-01
Option Card Input
(390H)
Selection
Contact Input
F3-03
Option DI-A3 Data
(3B9H)
Length Selection
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
V/f
OLV
Sets the time required to trigger a PG Open fault (PGo).
V/f
OLV
0: Disabled
1: Enabled
V/f
OLV
Sets the port for the PG option card used by motor 2.
0: CN5-C
1: CN5-B
V/f
OLV
Sets the number of pulses for a PG option card connected to port CN5-B.
V/f
OLV
0: Pulse A leads with Forward run command
1: Pulse B leads with Forward run command
V/f
OLV
Sets the division ratio for the pulse monitor used for the PG option card 2
installed to connector CN5-B. By setting "xyz", the division ratio becomes
= [(1 + x) / yz].
Setting range: 1 to 132 (1/32 to 1)
V/f
OLV
0: Disabled
1: Enabled
F2: Analog Input Card (AI-A3)
All Modes
0: Option card input terminals V1 and V2 replace drive analog input 1, 2,
and 3 terminals.
1: Input signals to terminals V1 and V2 are added together to create the
frequency reference.
All Modes
Sets the gain for the input signal to the analog card.
All Modes
Sets the bias for the input signal to the analog card.
F3: Contact Input Card (DI-A3)
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set
units (o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-
03.
All Modes
0: 8 bits
1: 12 bits
2: 16 bits
Description
CLV
CLV
CLV
CLV
CLV
CLV
CLV
1.3 Parameter Table
Setting
Default: 2.0 s
Min: 0.0 s
common
Max: 10.0 s
Default: 1
common
Min: 0
Max: 1
Default: 1
mm n
Min: 0
Max: 1
Default: 600 ppr
Min: 0 ppr
common
Max: 60000 ppr
Default: 0
common
Min: 0
Max: 1
common
Default: 1
Min: 1
Max: 132
Default: 1
common
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
Default: 100.0%
common_
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
Min: -999.9%
Max: 999.9%
common_
Default: 0
Min: 0
Max: 7
common_
Default: 2
Min: 0
Max: 2
page
158
160
160
158
159
159
160
160
160
160
161
161
41

Advertisement

Table of Contents
loading

Table of Contents