b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower
limit is disabled when set to 0.00%
No.
b5-34
b5-35: PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as
a bipolar limit.
No.
b5-35
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user-defined display of the PID
setpoint values and units for PID feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
b5-38
b5-39
b5-40: Frequency Reference Monitor Content During PID
Sets the content of the frequency reference monitor display (U1-01) when PID control is active.
No.
b5-40
Setting 0: Frequency Reference after PID
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference
Monitor U1-01 displays the frequency reference value.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Name
PID Output Lower Limit
Name
PID Input Limit
Name
PID Setpoint User Display
PID Setpoint Display Digits
Name
Frequency Reference Monitor Content during PID
Setting Range
-100.0 to 100.0%
0.0%
Setting Range
0 to 1000.0%
1000.0%
Setting Range
1 to 60000
Determined by b5-20
0 to 3
Determined by b5-20
Setting Range
0 or 1
0
2.2 b: Application
Default
Default
Default
Default
119