YASKAWA FSDrive-MV1000 Parameter Manual page 39

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
Motor 2 Motor
E4-08
Iron-Core
(344H)
Saturation
Coefficient 2
E4-09
Motor 2 Mechanical
(33FH)
Loss
E4-10
Motor 2 Iron Loss
(340H)
E4-11
Motor 2 Rated
(327H)
Power
<3> Parameter setting value is not reset to the default value when the drive is initialized (A1-03 = 1110/2220).
<6> Default setting value varies by the drive model (o2-04).
<10> Default setting is determined by the control mode (A1-02).
<16> Default setting is determined by the control mode (A1-02) and the drive model (o2-04).
<21> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.0.
<25> The default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<27> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<67> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning).
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
V/f
OLV
Set to the motor iron saturation coefficient at 75% of magnetic flux for
motor 2. This value is automatically set during Auto-Tuning.
V/f
OLV
Sets the motor mechanical loss for motor 2 as a percentage of motor rated
power (kW).
Adjust the setting in the following circumstances:
• When there is a large amount of torque loss due to motor bearing
friction
• When there is a large amount of torque loss in a fan or pump application
V/f
OLV
Sets the motor iron loss.
All Modes
Sets the motor rated capacity in kW. Automatically set during
Auto-Tuning.
Description
CLV
CLV
CLV
1.3 Parameter Table
Setting
Default: 0.75
common
Min: E4-07
Max: 0.75
common
Default: 0.0%
Min: 0.0%
Max: 10.0%
Default:
<6>
Min: 0 W
common
Max: 65535 W
common_
Default:
<6>
Min: 0 kW
Max: 65000 kW
page
157
157
157
157
39