YASKAWA FSDrive-MV1000 Parameter Manual page 124

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.3 C: Tuning
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a contact input (H1-
decel time 1 and 2 for motor 1, while C1-05 to C1-08 become accel/decel time 1 and 2 for motor 2. Accel/decel times 1
and 2 can be switched for each motor using a contact inputs set to H1-
Note: 1. The motor 2 selection function cannot be used when PM motor is used.
2. The contact input setting "Accel/Decel time 2 selection" (H1-
do so triggers an oPE03 error, indicating a contradictory multifunction input settings.
Accel/Decel Time 1 (H1-
Open
Closed
Switching Accel/Decel Times by a Frequency Level
The drive can switch between different acceleration and deceleration times automatically. The drive will switch from
accel/decel time 4 in C1-07 and C1-08 to the default accel/decel time in C1-01 and C1-02 (C1-05 and C1-06 for motor 2)
when the output frequency exceeds the frequency level set in parameter C1-11. When it falls below this level, the accel/
decel times are switched back.
Note: Acceleration and deceleration times selected by contact inputs have priority over the automatic switching by the frequency level
set to C1-11. For example, if accel/decel time 2 is selected, the drive will use this time only and not switch from accel/decel time
4 to the selected one.
Figure 2.22
C1-11: Accel/Decel Time Switching Frequency
Sets the frequency at which the drive switches between accel/decel time settings. Refer to
by a Frequency Level on page
No.
C1-11
<1> For details on the default settings, refer to
Note: Setting C1-11 to 0.0 Hz (0.0%) disables this function.
124
Table 2.13 Motor Switching and Accel/Decel Time Combinations
Motor 1 Selected
(Terminal set to H1-
= 7)
Accel
C1-01
C1-03
Figure 2.22
shows an operation example.
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-07
setting
When the output frequency ≥ C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)
Figure 2.22 Accel/Decel Time Switching Frequency
124.
Name
Accel/Decel Time Switching Frequency
Control Mode Dependent Parameter Default Values on page
= 16), parameters C1-01 to C1-04 become accel/
= 7 like shown in
= 1A) cannot be used together with motor 1/2 switching. Trying to
=16 OFF)
Decel
C1-02
C1-04
C1-01
C1-02
C1-08
setting
setting
setting
Setting Range
0.0 to 120.0 Hz
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Table
2.13.
Motor 2 Selected
(Terminal set to H1-
=16 ON)
Accel
Decel
C1-05
C1-06
C1-07
C1-08
Switching Accel/Decel Times
Default
Determined by A1-02
79.