2.7 H: Terminal Functions
H4-04, H4-14, H4-24, H4-34: Analog Output 1, 2, 3, 4 Cell Selection
Parameters H4-04, H4-14, H4-24, and H4-34 set the power cell numbers to be output from analog outputs 1 to 4. Their
settings are effective when 9
Monitor Selections).
No.
H4-04
H4-14
H4-24
H4-34
Figure 2.68
10 V
Output Voltage
5 V
0 V
0%
10 V
Output Voltage
3 V
0 V
0%
Using Gain and Bias to Adjust Output Signal Level
The meter can be calibrated while the drive is stopped.
The procedure for calibration is as follows.
194
(power cell) has been set for H4-01, H4-11, H4-21 and H4-31 (Analog Output 1 to 4
Name
Analog Output 1 Cell Selection
Analog Output 2 Cell Selection
Analog Output 3 Cell Selection
Analog Output 4 Cell Selection
H4-05, 15, 25, 35 = 0
100%
Monitor Value
H4-05, 15, 25, 35 = 0
100%
Monitor Value
Figure 2.68 Analog Output Gain and Bias Setting
Setting Range
1 to 15
1 to 15
1 to 15
1 to 15
Output Voltage
Gain 150%
Bias 0%
-100%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
Output Voltage
Bias 30%
Gain 100%
-100%
Bias 0%
Gain 100%
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
1
1
1
1
H4-05, 15, 25, 35 = 1
15 V
Gain = 150%
Bias = 0%
10 V
Gain = 100%
Bias = 0%
5 V
Gain = 50%
Bias = 0%
100%
Monitor Value
-5 V
-10 V
-15 V
H4-05, 15, 25, 35 = 1
15 V
Gain = 100%
Bias = 30%
10V
Gain = 100%
Bias = 0%
5 V
100%
Monitor Value
-5 V
-10 V
-15 V