YASKAWA FSDrive-MV1000 Parameter Manual page 30

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
C4-01
Torque
(215H)
Compensation Gain Sets the gain for the automatic torque (voltage) boost function and helps to
Torque
C4-02
Compensation
(216H)
Primary Delay
Time 1
Torque
C4-03
Compensation at
(217H)
Forward Start
Torque
C4-04
Compensation at
(218H)
Reverse Start
Torque
C4-05
Compensation Time
(219H)
Constant
Torque
C4-06
Compensation
(21AH)
Primary Delay
Time 2
C4-07
Motor 2 Torque
(341H)
Compensation Gain Sets the torque compensation gain used for motor 2.
C5-01
ASR Proportional
(21BH)
Gain 1
C5-02
ASR Integral Time
(21CH)
1
C5-03
ASR Proportional
(21DH)
Gain 2
C5-04
ASR Integral Time
(21EH)
2
C5-06
ASR Primary Delay
(220H)
Time Constant
ASR Gain
C5-07
Switching
(221H)
Frequency
C5-08
ASR Integral Limit
(222H)
C5-21
Motor 2 ASR
(356H)
Proportional Gain 1 Sets the proportional gain of the speed control loop (ASR) for motor 2.
C5-22
Motor 2 ASR
(357H)
Integral Time 1
30
C4: Torque Compensation
V/f
OLV
produce better starting torque. Used for motor 1.
V/f
OLV
Sets the torque compensation filter time.
V/f
OLV
Sets torque compensation at forward start as a percentage of motor torque.
V/f
OLV
Sets torque compensation at reverse start as a percentage of motor torque.
V/f
OLV
Sets the time constant for torque compensation at forward start and reverse
start (C4-03 and C4-04).
V/f
OLV
Sets the torque compensation time 2.
V/f
OLV
C5: Automatic Speed Regulator (ASR)
V/f
OLV
Sets the proportional gain of the speed control loop (ASR).
V/f
OLV
Sets the integral time of the speed control loop (ASR).
V/f
OLV
Sets the speed control gain 2 of the speed control loop (ASR).
V/f
OLV
Sets the integral time 2 of the speed control loop (ASR).
V/f
OLV
Sets the filter time constant for the time from the speed loop to the torque
command output.
V/f
OLV
Sets the frequency for switching between proportional gain 1, 2 and
integral time 1, 2.
V/f
OLV
Sets the ASR integral upper limit as a percentage of rated load torque.
V/f
OLV
V/f
OLV
Sets the integral time of the speed control loop (ASR) for motor 2.
Description
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting
Default:
<10>
common
Min: 0.00
Max: 2.50
Default:
<16>
Min: 0 ms
common
Max: 60000 ms
Default: 0.0%
Min: 0.0%
common
Max: 200.0%
Default: 0.0%
Min: -200.0%
common
Max: 0.0%
Default: 10 ms
common
Min: 0 ms
Max: 200 ms
Default: 150 ms
Min: 0 ms
common
Max: 10000 ms
Default: 1.00
Min: 0.00
common
Max: 2.50
Default:
<10>
Min: 0.00
common
Max: 300.00
Default:
<10>
Min: 0.000 s
common
Max: 10.000 s
Default:
<10>
Min: 0.00
common
Max: 300.00
Default:
<10>
Min: 0.000 s
common
Max: 10.000 s
Default:
<10>
common
Min: 0.000 s
Max: 0.500 s
Default:
<10>
common
Min: 0.0 Hz
Max: 120.0 Hz
Default: 200%
Min: 0%
common
Max: 400%
Default:
<15>
Min: 0.00
common
Max: 300.00
Default:
<15>
Min: 0.000 s
common
Max: 10.000 s
page
129
130
130
130
130
130
130
132
<17>
132
132
<17>
132
133
133
133
134
<17>
134