The slip compensation limit is constant throughout the constant torque range (frequency reference
constant power range (frequency reference ≥ E1-06), it is increased based on C3-03 and the output frequency as shown in
the following diagram.
Figure 2.24
C3-04: Slip Compensation Selection during Regeneration
Enables or disables slip compensation during regenerative operation.
Even if enabled, this function does not operate when the output frequency is too low.
No.
C3-04
Slip Compensation Selection during Regeneration
Setting 0: Disabled
Slip compensation is not provided. Depending on the load and mode of operation, the actual motor speed will be lower or
higher than the frequency reference.
Setting 1: Enabled (6 Hz and above)
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)
Slip compensation is enabled during regenerative operation, and at frequencies as low as 2 Hz. The drive uses the motor
rated slip set in E2-02 to automatically calculate the frequency range where compensation will be disabled.
C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when the output voltage reaches the saturation range.
If the input power supply voltage is low or the motor has a high voltage rating, this function can help improve the speed
precision when moving heavy loads at high speeds. When this function is enabled, the reduction in flux causes a slightly
higher current to compensate the torque. Keep this in mind when selecting the drive.
No.
C3-05
Output Voltage Limit Operation Selection
<1> For details on the default settings, refer to
Setting 0: Disabled
Setting 1: Enabled
C3-16: Output Voltage Limit Operation Start Level (Percentage Modulation)
Sets the output voltage limit operation start level (percentage modulation) when C3-05 is enabled.
No.
Output Voltage Limit Operation Start Level
C3-16
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
E1-04
E1-06 × C3-03
C3-03
common_TMonly
Figure 2.24 Slip Compensation Limit
Name
Name
Control Mode Dependent Parameter Default Values on page
Name
(Percentage Modulation)
Output Frequency
E1-06
E1-04
Base
Maximum
Frequency
Frequency
Setting Range
0 to 2
Setting Range
0 or 1
Setting Range
70.0 to 90.0%
2.3 C: Tuning
E1-06). In the
Default
0
Default
Determined by A1-02
<1>
79.
Default
85.0%
127