2.10 o: Operator Related Settings
o2-04: Drive Capacity Selection
This parameter must be set when replacing the controller for any reason. For information on the drive model selection,
see
Defaults by Drive Model Selection (o2-04) on page
NOTICE: Drive performance will suffer if the correct drive capacity is not set for o2-04, and protective functions will fail to operate
properly.
No.
o2-04
Drive Capacity Selection
Note: Change settings only when necessary.
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in
the Drive Mode.
No.
Frequency Reference Setting Method
o2-05
Setting 0: ENTER key required
Every time the frequency reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed with the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after
remaining unchanged for 5 seconds.
o2-06: Operation Selection when Digital Operator is Disconnected
Determines if the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set to
0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
Operation Selection when Digital
o2-06
Operator is Disconnected
Setting 0: Disabled
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an "oPr" fault is triggered. The motor coasts to stop.
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction in which the motor will rotate after the drive is powered up and the Run command is given from
the digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
No.
Motor Direction at Power Up when Using
o2-07
Setting 0: Forward
Setting 1: Reverse
224
Name
Name
0 or 1
Selection
Name
0 or 1
Name
0 or 1
Operator
82.
Setting Range
Setting Range
Setting Range
Setting Range
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
Determined by drive capacity
Default
0
Default
0
Default
0