◆ b6: Dwell Function

The Dwell function is used to temporarily hold the frequency reference at a predefined value for a set time, then continue
accelerating or decelerating.
The Dwell function can help prevent speed loss when starting and stopping a heavy load.
The figure below shows how the Dwell function works.
Note: Using the Dwell function requires that the stopping method for the drive be set to "Ramp to stop" (b1-03 = 0).
Figure 2.18
b6-01, b6-02: Dwell Reference, Dwell Time at Start
Parameter b6-01 determines the frequency that is held for the time set in b6-02 during acceleration.
No.
b6-01
b6-02
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> For details on the default settings, refer to
b6-03, b6-04: Dwell Reference, Dwell Time at Stop
Parameter b6-03 determines the frequency that is held for the time set in b6-04 during deceleration.
No.
b6-03
b6-04
<1> Range upper limit is determined by the maximum output frequency (E1-04) and the upper limit of the frequency reference (d2-01).
<2> For details on the default settings, refer to
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
OFF
ON
Run Command
b6-01
Output Frequency
b6-02
Figure 2.18 Dwell Function at Start and Stop
Name
Dwell Reference at Start
Dwell Time at Start
Control Mode Dependent Parameter Default Values on page
Name
Dwell Reference at Stop
Dwell Time at Stop
Control Mode Dependent Parameter Default Values on page
OFF
common_TMonly
b6-03
b6-04
Setting Range
0.0 to 120.0 Hz
<1>
0.0 to 10.0 s
79.
Setting Range
0.0 to 120.0 Hz
<1>
0.0 to 10.0 s
79.
2.2 b: Application
Default
Determined by A1-02
<2>
0.0 s
Default
Determined by A1-02
<2>
0.0 s
121