YASKAWA FSDrive-MV1000 Parameter Manual page 63

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
Mechanical
L6-11
Weakening
(46BH)
Detection Start
Time
L7-01
Forward Torque
(4A7H)
Limit
L7-02
Reverse Torque
(4A8H)
Limit
Forward
L7-03
Regenerative
(4A9H)
Torque Limit
Reverse
L7-04
Regenerative
(4AAH)
Torque Limit
Torque Limit
L7-06
Integral Time
(4ACH)
Constant
Torque Limit
L7-07
Control Method
(4C9H)
Selection during
Accel/Decel
L7-16
Torque Limit
(44DH)
Process at Start
Regenerative
L7-30
Torque Limit Mode
(1FDH)
Selection
L8-02
Overheat Alarm
(4AEH)
Level
L8-03
Overheat Pre-Alarm
(4AFH)
Operation Selection
L8-07
Output Phase Loss
(4B3H)
Protection Selection
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
All Modes
Sets the operation time (U1-04) required before Mechanical Weakening
Detection is active.
L7: Torque Limit
V/f
OLV
Sets the torque limit value as a percentage of the motor rated torque.
Four individual quadrants can be set.
Output Torque
L7-04
Regeneration
REV
L7-02
V/f
OLV
Sets the integral time constant for the torque limit. Increase the setting for
faster torque limit response.
V/f
OLV
0: Proportional control (changes to integral control at constant speed).
Use this setting when acceleration to the desired speed should take
precedence over the torque limit.
1: Integral control.
Set L7-07 to 1 if the torque limit should take precedence.
V/f
OLV
0: A delay time is disabled
1: A delay time is enabled
V/f
OLV
Sets the mode for the regenerative torque limit.
0: Standard mode (torque limits entered from all analog inputs and
through communications effective)
1: Independent mode (only the torque limits set with L7-03, L7-04, and
regenerative torque limit effective (H3-
L8: Drive Protection
All Modes
An overheat pre-alarm will occur if the thermistor temperature exceeds the
level set in L8-02.
All Modes
0: Ramp to stop. A fault is triggered.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09. A
fault is triggered.
3: Continue operation. An alarm is triggered.
4: Continue operation at reduced speed as set in L8-19.
Note:
0 to 2 are recognized as faults, and 3 and 4 as alarms.
All Modes
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Triggered when the output current falls below 5% of the drive rated
current.
Output phase loss detection can mistakenly be triggered if the motor rate
current is very small comparing with the drive capacity. Disable this
parameter in such case.
Description
CLV
Positive Torque
L7-01
Motor
r/min
FWD
Regeneration
L7-03
Negative Torque
CLV
CLV
CLV
CLV
= 12)
1.3 Parameter Table
Setting
Default: 0 h
common_
Min: 0 h
Max: 65535 h
Default: 100%
common
Min: 0%
Max: 300%
Default: 100%
Min: 0%
Max: 300%
Default: 1%
Min: 0%
Max: 300%
Default: 1%
Min: 0%
Max: 300%
Default: 200 ms
common
Min: 5 ms
Max: 10000 ms
common
Default: 0
Min: 0
Max: 1
Default: 1
common
Min: 0
Max: 1
common
Default: 0
Min: 0
Max: 1
Default:
common_
<6>
Min: 50°C
Max: 150°C
common_
Default: 3
Min: 0
Max: 4
common_
Default: 2
Min: 0
Max: 2
Page
210
210
210
210
210
211
211
211
211
212
212
213
63