YASKAWA FSDrive-MV1000 Parameter Manual page 189

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

H3-09: Analog Input 2 Signal Level Selection
Selects the input signal level for analog input 2.
No.
H3-09
Analog Input 2 Signal Level Selection
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. Refer to
Setting 1: -10 to 10 Vdc
The input level is -10 to 10 Vdc. Refer to
H3-10: Analog Input 2 Function Selection
Parameter H3-10 sets the function assigned to analog input 2. Refer to
details.
No.
H3-10
H3-11, H3-12: Analog Input 2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input at analog input 2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V input at analog input 2.
Both can be used to adjust the characteristics of the analog input signal at analog input 2. The setting works in the same
way as parameters H3-03 and H3-04 for analog input 1.
No.
H3-11
H3-12
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs 1 and 2.
An analog input filter can be used to prevent erratic drive control when a "noisy" analog reference is used. The drive
operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing
analog signals.
No.
H3-13
H3-14: Analog Input Terminal Enable Selection
When one of the contact input parameters is set for "Analog input enable" (H1-
determines which analog input terminals are enabled and which terminals are disabled when the input is closed.
All analog input terminals will be enabled all of the time if H1-
No.
H3-14
Analog Input Terminal Enable Selection
Setting 1: All analog input terminals enabled
Setting 2: Only analog input 2 enabled
Setting 3: Only analog input 1 and 2 enabled
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Name
Setting 0: 0 to 10 Vdc on page
Setting 1: -10 to 10 Vdc on page
Name
Analog Input 2 Function Selection
Name
Analog Input 2 Gain
Analog Input 2 Bias
Name
Analog Input Filter Time Constant
Name
2.7 H: Terminal Functions
Setting Range
0 or 1
187.
187.
Analog Input Terminal Settings on page 190
Setting Range
0 to 32
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
= C), the value set for H3-14
is not set to C.
Setting Range
1 to 3
Default
1
for
Default
0
Default
100.0%
0.0%
Default
0.03 s
Default
3
189

Advertisement

Table of Contents
loading

Table of Contents