YASKAWA FSDrive-MV1000 Parameter Manual page 58

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
H5-01
Drive Node
(425H)
Address
<32>
H5-02
Communication
(426H)
Speed Selection
H5-03
Communication
(427H)
Parity Selection
Stopping Method
H5-04
After
(428H)
Communication
Error (CE)
Communication
H5-05
Fault Detection
(429H)
Selection
H5-06
Drive Transmit
(42AH)
Wait Time
H5-07
RTS Control
(42BH)
Selection
H5-09
CE Detection Time Sets the time required to detect a communications error.
(435H)
Communications
H5-11
ENTER Function
(43CH)
Selection
H5-12
Run Command
(43DH)
Method Selection
<32> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<38> For details, refer to the FSDrive-MV1000 Instruction Manual (Manual No. EZZ010926).
Note: The settings for MEMOBUS/Modbus communications only become available once the power has been turned OFF and back ON
again.
58
H5: MEMOBUS/Modbus Serial Communication
All Modes
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
All Modes
0: No parity
1: Even parity
2: Odd parity
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
All Modes
0: Disabled
1: Enabled. If communication is lost for more than the time set in H5-09, a
CE fault will occur.
All Modes
Set the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Adjustment may be needed when networking several drives.
All Modes
0: Drive requires an Enter command before accepting any changes to
parameter settings.
1: Parameter changes are activated immediately without the Enter
command.
All Modes
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
Description
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting
Default: 1F
common_
Min: 0
Max: FFH
common_
Default: 3
Min: 0
Max: 8
common_
Default: 0
Min: 0
Max: 2
common_
Default: 3
Min: 0
Max: 3
common_
Default: 1
Min: 0
Max: 1
Default: 5 ms
common_
Min: 5 ms
Max: 65 ms
Default: 1
common_
Min: 0
Max: 1
common_
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
Page
<38>
<38>
<38>
<38>
<38>
<38>
<38>
<38>
<38>
<38>