B: Application; B1: Operation Mode Selection - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.2

b: Application

◆ b1: Operation Mode Selection

b1-01: Frequency Reference Selection 1
Parameter b1-01 determines the frequency reference source in the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will flash.
2. Press the
No.
b1-01
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-
• entering the frequency reference on the operator keypad.
For details on how to change the setting value for the frequency reference, refer to the FSDrive-MV1000 Instruction
Manual (Manual No. EZZ010926).
Setting 1: Terminals (analog input terminals)
Using this setting, analog frequency references can be input as a voltage signal from analog input 1 or 2.
For details on the setting, refer to
Table 2.6 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
Signal Level
0 to 10 Vdc
Analog input 1
-10 to +10 Vdc
0 to 10 Vdc
Analog input 2
-10 to +10 Vdc
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Name
Frequency Reference Selection 1
Table
2.6.
Parameter Settings
Signal Level
Function
Selection
Selection
H3-01 = 0
H3-02 = 0
(Master Speed
Frequency
H3-01 = 1
Reference)
H3-09 = 0
H3-10 = 0
(Master Speed
Frequency
H3-09 = 1
Reference)
Setting Range
0 to 3
parameters.
Gain
Bias
H3-03
H3-04
H3-11
H3-12
2.2 b: Application
Default
1
Notes
95

Advertisement

Table of Contents
loading