No.
Name
(Addr.)
Speed Search
b3-10
Detection
(19AH)
Compensation Gain
(Speed Estimation)
Speed Search
b3-11
Method Switching
(19BH)
Level
(Speed Estimation)
Speed Search
b3-17
Restart Current
(1F0H)
Level
Speed Search
b3-18
Restart Detection
(1F1H)
Time (Speed
Estimation)
b3-19
Number of Speed
(1F2H)
Search Restarts
b3-25
Speed Search Wait
(1C8H)
Time
Torque
b3-30
Compensation Time
(30B0H)
Constant during
Speed Search
Current
b3-31
Suppression Start
(30B1H)
Level during
Voltage Recovery
Current
b3-32
Suppression Time
(30B2H)
Constant during
Voltage Recovery
Recovery Waiting
b3-33
Time after Speed
(30B3H)
Search Completion
Software CLA
b3-34
Current Limit Value
(30B4H)
1 during Speed
Search
Software CLA
b3-35
Current Limit Value
(30B5H)
2 during Speed
Search
b4-01
Timer Function On-
(1A3H)
Delay Time
b4-02
Timer Function
(1A4H)
Off-Delay Time
24
V/f
OLV
Sets the gain which is applied to the speed detected by Speed Estimation
Speed Search before the motor is reaccelerated. Increase this setting if ov
occurs when performing Speed Search after a relatively long period of
baseblock.
All Modes
Sets the switching level when the search method is automatically switched
in accordance with the size of the motor's residual voltage.
V/f
OLV
Sets the Speed Search restart current level as a percentage of the drive
rated current.
V/f
OLV
Sets the time to detect Speed Search restart.
V/f
OLV
Sets the number of times the drive can attempt to restart when performing
Speed Search.
V/f
OLV
Sets the time the must wait between each Speed Search restart attempt.
V/f
OLV
Sets the primary delay time of the torque compensation function during
Speed Search, in ms units.
V/f
OLV
Sets the level at which to start the operation to extend the voltage recovery
time in order to suppress the current when the voltage is recovered during
Speed Search. The setting is made by taking the motor's no-load current to
be 1.0.
V/f
OLV
Sets the time constant to filter the level for extending the voltage recovery
time in order to suppress the current when the voltage is recovered during
Speed Search.
V/f
OLV
Sets the waiting time between the end of Speed Search and the switch to
normal control. The frequency reference is maintained during this time.
V/f
OLV
Sets the software's current limit value during Speed Search. Set as a
percentage of the motor's rated current.
V/f
OLV
Sets the current limit value for the software when the frequency reference
value is 0 Hz during Speed Search. Set as a percentage of the motor rating.
b4: Timer Function
All Modes
Sets the on-delay and off-delay times (dead-band width) of the timer
function output at the contact output (H2-
function input at the contact input (H1-
Description
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
=12) in relation to the time
=18).
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Setting
common
Default: 1.05
Min: 1.00
Max: 1.20
Default:
common_
<6>
Min: 0.5
Max: 100.0
Default: 120%
common
Min: 0%
Max: 200%
Default: 0.10 s
Min: 0.00 s
common
Max: 1.00 s
Default: 3
common
Min: 0
Max: 10
Default: 0.5 s
Min: 0.0 s
common
Max: 30.0 s
Default: 10 ms
common
Min: 0 ms
Max: 10000 ms
common
Default: 1.5
Min: 0.0
Max: 5.0
Default: 5 ms
common
Min: 0 ms
Max: 100 ms
Default: 0.01 s
common
Min: 0.00 s
Max: 5.00 s
Default: 95.0%
common
Min: 0.0%
Max: 300.0%
Default: 90.0%
common
Min: 0.0%
Max: 300.0%
Default: 0.0 s
Min: 0.0 s
common_
Max: 3000.0 s
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
page
107
107
107
107
107
107
108
108
108
108
108
108
109
109