YASKAWA FSDrive-MV1000 Parameter Manual page 53

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

H2-
Function
Setting
13
Speed Agree 2
14
User-set Speed Agree 2
15
Frequency Detection 3
16
Frequency detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During baseblock (N.C.)
1C
Motor 2 Selection
1D
During Regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1) Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this
Drive overheat pre-alarm
20
(oH)
Mechanical Weakening
22
detection (N.O.)
2F
Maintenance Period
30
During Torque Limit
31
During Speed Limit
During Speed Limit in Torque
32
Control
37
During Frequency Output
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
H2 Contact Output Settings
All Modes
Closed: When drive output frequency equals the frequency reference ±L4-04.
All Modes
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
All Modes
Closed: When the drive output frequency is less than or equal to the value in L4-03
±L4-04.
All Modes
Closed: When the output frequency is greater than or equal to the value in L4-03
±L4-04.
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Overtorque or undertorque has been detected.
All Modes
Open: Overtorque or undertorque has been detected.
All Modes
Closed: Drive is running in the reverse direction.
All Modes
Open: Drive has entered the baseblock state (no output voltage).
All Modes
Closed: Motor 2 is selected by a contact input (H1-
V/f
OLV
Closed: Motor is regenerating energy into the drive.
All Modes
Closed: An automatic restart is performed
All Modes
alarm.
All Modes
Closed: Thermistor temperature exceeds the parameter L8-02 value.
All Modes
Closed: Mechanical weakening detected.
All Modes
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
V/f
OLV
Closed: When the torque limit has been reached.
V/f
OLV
Closed: Speed limit has been reached.
V/f
OLV
Closed: Speed limit has been reached while using Torque Control.
All Modes
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not
being performed).
Description
common_
common_
common_
common_
common_
common_
common_
common_
common_
common
= 16).
CLV
common
common_
common_
common_
common_
common_
CLV
common
CLV
common
CLV
common
common_
1.3 Parameter Table
Reference
page
182
183
183
184
181
181
181
184
184
185
185
185
185
185
185
185
185
185
185
186
53