d4-08: Frequency Reference Bias Upper Limit (Up/Down 2)
Parameter d4-08 sets the upper limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter
d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.
Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the
frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. From that point, the bias can
be increased up to the limit set in d4-08 again.
No.
d4-08
d4-09: Frequency Reference Bias Lower Limit (Up/Down 2)
Parameter d4-09 sets the lower limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter
d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.
Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the
frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. If the bias is increased using
the Up 2 command, it cannot be reduced with a Down 2 command when the limit set in d4-09 is 0. To allow speed reduction in
this situation, set a negative lower limit in d4-09.
No.
d4-09
d4-10: Up/Down Frequency Reference Limit Selection
Selects how the lower frequency limit is set when the Up/Down function is used. Refer to
command on page 168
for details on the Up/Down function in combination with frequency reference limits.
No.
d4-10
Setting 0: Lower Limit is Determined by d2-02 or Analog Input
The lower frequency reference limit is determined by the higher value of either parameter d2-02 or an analog input 1, 2
that is programmed for "Frequency bias".
Note: For example, if the command to switch the external reference (H1-
an analog input as the reference source, then the analog value would become the lower reference limit when the Up/Down
command is active. Change d4-10 to 1 to make the Up/Down function independent of the analog input value.
Setting 1: Lower Limit is Determined by Parameter d2-02
Only parameter d2-02 sets the lower frequency reference limit.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Name
Frequency Reference Bias Upper Limit (Up/Down 2)
Name
Frequency Reference Bias Lower Limit (Up/Down 2)
Name
Up/Down Frequency Reference Limit Selection
2.4 d: Reference Settings
Setting Range
0.0 to 100.0%
Setting Range
−99.9 to 0.0%
Setting 10, 11: Up, Down
Setting Range
0 or 1
= 2) is used to switch between the Up/Down function and
Default
100.0%
Default
0.0%
Default
0
143