Table 1.5 3 kV Class Drives Default Settings by Drive Model Selection
No.
Name
<61>
Model
CIMR-MV2
Drive Model
o2-04
Selection
E2-11(E4-11)
Motor Rated Power kW
V/f Gain during Speed
b3-04
Search
Output Current 1 during
b3-06
Speed Search
Speed Search Method
b3-11
Switching Level (Speed
Estimate Speed Search)
E2-01(E4-01)
Motor Rated Current
E2-02(E4-02)
Motor Rated Slip
E2-03(E4-03) Motor No-Load Current
Motor Line-to-Line
E2-05(E4-05)
Resistance
Motor Leakage
E2-06(E4-06)
Inductance
Motor Iron Loss for
E2-10(E4-10)
Torque Compensation
Momentary Power Loss
L2-02
Ride-Thru Time
Momentary Power Loss
L2-03
Minimum Baseblock
Time
Momentary Power Loss
L2-04
Voltage Recovery Time
Undervoltage Detection
L2-05
Level (Uv)
L8-02
Overheat Alarm Level
<62>
Output Ground Fault
L8-09
Detection Selection
FAN Board Use
L8-33
Selection
Transformer Overheat
L8-87
Alarm (TMA) Level
Transformer Overheat
L8-88
Fault (TME) Level
Hunting Prevention Time
n1-03
Constant
Output Current Detection
n9-02
Gain
Input Current
n9-71
Conversion Coefficient
Reference Voltage for
o2-11
Input Voltage Detection
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Unit
035
050
070
20
21
22
160
230
320
%
80
80
80
0.5
0.5
0.5
%
5.0
5.0
5.0
A
30.0
45.0
60.0
Hz
0.25
0.25
0.25
A
8.0
11.0
15.0
W
0.300
0.300
0.300
%
20.0
20.0
20.0
W
0
0
0
sec
2.0
2.0
2.0
sec
2.0
2.0
2.0
sec
3.0
3.0
3.0
V
940
940
940
105
105
105
1
1
1
1
1
1
°C
150
150
150
°C
140
140
140
ms
30
30
30
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
0.0340 0.0340 0.0235 0.0150 0.0094 0.0060 0.0060 0.0044 0.0030 0.0020 0.0020
V
3300
3300
3300
1.5 Defaults by Drive Model Selection (o2-04)
Default Settings
100
140
200
260
23
24
25
26
460
640
910
1190
80
80
80
80
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
85.0
120.0
170.0
220.0
0.25
0.25
0.25
0.25
21.0
30.0
43.0
55.0
0.300
0.300
0.300
0.300
20.0
20.0
20.0
20.0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
940
940
940
940
105
105
105
95
1
1
1
1
1
1
2
2
150
150
150
150
140
140
140
140
30
30
30
30
3300
3300
3300
3300
330
400
520
650
27
28
29
2A
1510
1830
2380
2970
80
80
80
80
0.5
0.5
0.5
0.5
5.0
5.0
5.0
5.0
280.0
340.0
440.0
550.0
0.25
0.25
0.25
0.25
70.0
85.0
110.0
138.0
0.300
0.300
0.300
0.300
20.0
20.0
20.0
20.0
0
0
0
0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
940
940
940
940
105
105
105
105
1
1
1
1
2
2
2
2
150
150
150
150
140
140
140
140
30
30
30
30
3300
3300
3300
3300
83