A3: Trace Data - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.1 A: Initialization

◆ A3: Trace Data

A3-01 to A3-32: Trace Data 01 to 32
Sets the numbers of the monitor items to be registered as the trace data. A maximum of 32 items can be set.
Note: 1. Set this parameter to the last three digits
current).
2. Set 000 if the parameter is not used.
3. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
A3-01 to A3-32
<1> For details on the default settings, refer to
A3-33: High-Speed Trace Sampling Time
Sets the sampling time for high-speed tracing in 0.001 s units. Note, however, that if 0.000 s is set the setting made will
actually be 0.00025 s (250 μs).
Note: 1. The maximum number of sampling points for high-speed tracing is 4000 per item.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
A3-33
High-Speed Trace Sampling Time
A3-34: Low-Speed Trace Sampling Time
Sets the sampling time for low-speed tracing in 0.01s units.
Note: 1. The maximum number of sampling points for low-speed tracing is 500 per item.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
A3-34
Low-Speed Trace Sampling Time
A3-35: Number of Data after High-Speed-Trace Fault Detection
Sets the number of samplings of the data to be registered after a fault is detected in high-speed tracing.
Note: 1. Only effective when a fault has been detected and operation automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
Number of Data after High-Speed-Trace
A3-35
A3-36: Number of Data after Low-Speed-Trace Fault Detection
Sets the number of samplings of the data to be registered after a fault is detected in low-speed tracing.
Note: 1. Only effective when a fault has been detected and operation automatically stopped.
2. When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
Number of Data after Low-Speed-Trace Fault
A3-36
A3-37: Trace Stop Selection
Sets the condition to stop tracing.
Note: When a CPF00, CPF01, CPF06, Uv1, oFA00, oFb00, or oFC00 fault occurs, no fault trace is performed.
No.
A3-37
Setting 0: Error always detected and drive stopped
Setting 1: Error detected and drive stopped during run only
94
-
Name
Trace Data 01 to 32
Control Mode Dependent Parameter Default Values on page
Name
Name
Name
Fault Detection
Name
Detection
Name
Trace Stop Selection
of the desired U -
parameter. For example, enter "103" for U1-03 (output
Setting Range
0 to 899
Setting Range
0.000 to 10.000 s
Setting Range
0.01 to 60.00 s
Setting Range
0 to 250
Setting Range
0 to 250
Setting Range
0 or 1
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Default
Determined by A1-02
<1>
79.
Default
0.000 s
Default
0.05 s
Default
200
Default
50
Default
0