When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run
command may already be present at the location the source was switched to. Parameter b1-07 can be used to determine
how the Run command is treated in this case.
No.
b1-07
Setting 0: Run command must be cycled
When the Run command source is different in the old and new source (e.g., the old source was the terminals and the new
source is serial communication), and the Run command is active at the new source as the switch over occurs, the drive
will not start or will stop operation if it was running before. The Run command has to be re-input at the new source in
order to start the drive again.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was running before.
WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating
machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
b1-08: Run command selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-
Tuning Mode).
No.
b1-08
Run Command Selection while in Programming Mode 0 to 2
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1-15: Frequency Reference Selection 2
Refer to
b1-01: Frequency Reference Selection 1 on page
No.
b1-15
b1-16: Run Command Selection 2
Refer to
b1-02: Run Command Selection 1 on page
No.
b1-16
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Name
LOCAL/REMOTE Run Selection
Name
Name
Frequency Reference Selection 2
96.
Name
Run Command Selection 2
Setting Range
0 or 1
Setting Range
95.
Setting Range
0 to 3
Setting Range
0 to 3