2.2 b: Application
The time for DC Injection Braking is determined by the value set in b2-04 and by the output frequency at the time the
Stop command is input or the Run command is turned OFF. It can be calculated by:
Figure 2.3
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to a stop, lengthen the minimum baseblock time (L2-03) until the
fault no longer occurs.
Setting 3: Coast to Stop with Timer
When a Stop command is input or the Run command is turned OFF, the drive will turn off its output and the motor will
coast to a stop. If a Run command is input before the time t has elapsed, the drive will not start.
Figure 2.4
The wait time t is determined by the output frequency when the Stop command is input and by the active deceleration
time.
Figure 2.5
98
DC Injection brake time
DC Injection braking time
b2-04 10
b2-04
10%
Figure 2.3 DC Injection Braking Time Depending on Output Frequency
Run command
ON
Output
frequency
Figure 2.4 Coast to Stop with Timer
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
Min output
Figure 2.5 Run Wait Time Depending on Output Frequency
(b2-04) × 10 × Output frequency
=
Max. output frequency (E1-04)
Output frequency when
Stop command was entered
OFF
ON
Drive output shut off
Run wait time t
Output frequency
frequency
when Stop command
was entered
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide