No.
Name
(Addr.)
d6-01
Field Weakening
(2A0H)
Level
d6-02
Field Weakening
(2A1H)
Frequency Limit
d6-03
Field Forcing
(2A2H)
Selection
d6-06
Field Forcing Limit Sets the upper limit of the excitation current command during magnetic
(2A5H)
d7-01
(2B2H)
Offset Frequency 1 Added to the frequency reference when the contact input "Offset
d7-02
(2B3H)
Offset Frequency 2 Added to the frequency reference when the contact input "Offset
d7-03
(2B4H)
Offset Frequency 3 Added to the frequency reference when the contact input "Offset
<10> Default setting is determined by the control mode (A1-02).
<20> Range upper limit is determined by the maximum output frequency (E1-04) and the upper limit of the frequency reference (d2-01).
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
d6: Field Weakening and Field Forcing
V/f
OLV
Sets the drive output voltage for the Field Weakening function as a
percentage of the maximum output voltage.
Enabled when a contact input is set for Field Weakening (H1-
V/f
OLV
Sets the lower limit of the frequency range where Field Weakening control
is valid.
The Field Weakening command is valid only at frequencies above this
setting and only when the output frequency matches the frequency
reference (speed agree).
V/f
OLV
0: Disabled
1: Enabled
V/f
OLV
field forcing. A setting of 100% is equal to motor no-load current.
Disabled only during DC Injection Braking.
d7: Offset Frequency
All Modes
Frequency 1" (H1-
= 44) is switched on. Set as a percentage of the
maximum output frequency.
All Modes
Frequency 2" (H1-
= 45) is switched on. Set as a percentage of the
maximum output frequency.
All Modes
Frequency 3" (H1-
= 46) is switched on. Set as a percentage of the
maximum output frequency.
Description
CLV
CLV
CLV
CLV
1.3 Parameter Table
Setting
Default: 80%
common
Min: 0%
Max: 100%
= 63).
common
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
Default: 0
common
Min: 0
Max: 1
Default: 200%
common
Min: 100%
Max: 400%
common_
Default: 0.0%
Min: -100.0%
Max: 100.0%
common_
Default: 0.0%
Min: -100.0%
Max: 100.0%
common_
Default: 0.0%
Min: -100.0%
Max: 100%
page
149
149
149
149
150
150
150
35