2.7 H: Terminal Functions
Setting 37: During frequency output
Output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being executed: baseblock, DC Injection Braking.
Closed
Drive is outputting the frequency.
Figure 2.61
Setting 38: Drive enable
A contact output set for "Drive enable" will reflect the status of a contact input configured as "Drive enable" input (H1-
= 6A). If that contact input closes, then the contact output set for "Drive enable" will also close.
Setting 39: Watt hour pulse output
Outputs a pulse to indicate the watt hours. Refer to
Setting 3A: Cooling Fan, Transformer Abnormal Temperature Rise
Output closes whenever no abnormal temperature rise in the cooling fans or transformers has occurred.
Setting 3C: LOCAL/REMOTE status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as the
Open
frequency reference and Run command source
Closed
LOCAL: The digital operator is used as the frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed. Refer to
Setting 3E: PID feedback low
The set output terminal closes when a PID feedback loss (FbL) is detected. The feedback is considered to be lost if it falls
below the level set in b5-13 for longer than the time set in b5-14. Refer to
details.
Setting 3F: PID feedback high
The set output terminal closes when a PID feedback high (FbH) is detected. The feedback is considered to be high if it
exceeds the level set in b5-36 for longer than the time set in b5-37. Refer to
for details.
Setting 4C: During Fast Stop
Output terminal closes when a Fast Stop is being executed. Refer to
Setting 4D: oH pre-alarm time limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not cleared after ten frequency reduction operation cycles. Refer to
Selection on page 212
for a more detailed description.
Setting 60: Drive Cooling Fan Alarm
Output closes when the drive's cooling fan has failed.
186
OFF
ON
Run command
OFF
Baseblock
command
Output
frequency
During frequency
OFF
output
Figure 2.61 During Frequency Output Time Chart
Description
ON
(closed)
ON
H2-17: Watt Hour Output Unit Selection on page 187
Description
b3: Speed Search on page 103
PID Feedback Loss Detection on page 115
Setting 15, 17: Fast Stop (N.O., N.C.) on page
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
common_TMonly
PID Feedback Loss Detection on page 115
L8-03: Overheat Pre-Alarm Operation
for details.
for details.
for
170.