B4: Delay Timers - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

◆ b4: Delay Timers

The timer function is independent of drive operation and can be used to delay the switching of a contact output triggered
by a contact input signal. An on-delay and off-delay can be separately set. The delay timer can help to get rid of
chattering switch noise from sensors.
To enable the timer function, a contact input must be set to "Timer input" (H1-
to "Timer output" (H2-
b4-01, b4-02: Timer Function On-Delay, Off-Delay Time
Parameter b4-01 sets the on-delay time for switching the timer output. Parameter b4-02 sets the off-delay time for
switching the timer output.
No.
b4-01
b4-02
Timer Function Operation
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer
function input is open for longer than the value set in b4-02, the timer output function switches off. The following
diagram demonstrates the timer function operation.
Figure 2.14
Contact Input: Timer Function
Contact Output: Timer Function
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
=12). One timer can be used only.
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
ON
ON
b4-01
Figure 2.14 Timer Operation
Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s
ON
b4-02
b4-01
2.2 b: Application
=18) and a contact output must be set
Default
0.0 s
0.0 s
On (Closed)
Off (Open)
On (Closed)
ON
Off (Open)
common_TMonly
b4-02
109

Advertisement

Table of Contents
loading

Table of Contents