YASKAWA FSDrive-MV1000 Parameter Manual page 67

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
User-Set Display
o1-10
Units Maximum
(520H)
Value
User-set Display
o1-11
Units Decimal
(521H)
Display
o2-01
LO/RE Key
(505H)
Function Selection
o2-02
STOP Key Function
(506H)
Selection
o2-03
User Parameter
(507H)
Default Value
o2-04
Drive Model
(508H)
Selection
Frequency
o2-05
Reference Setting
(509H)
Method Selection
Operation Selection
o2-06
when Digital
(50AH)
Operator is
Disconnected
Motor Direction at
o2-07
Power Up when
(527H)
Using Operator
Initialization
o2-09
Specification
(50DH)
Selection
Reference Voltage
o2-11
for Input Voltage
(50FH)
Detection
o3-01
Copy Function
(515H)
Selection
o3-02
Copy Allowed
(516H)
Selection
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output
frequency.
o1-11 sets the position of the decimal position.
o2: Digital Operator Keypad Functions
All Modes
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE
operation.
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
All Modes
Enter the drive model. Setting required only if installing a new control
board.
All Modes
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted
using the up and down arrow keys only.
All Modes
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
All Modes
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital
operator.
All Modes
Sets the primary rated voltage of the transformer.
o3: Copy Function
All Modes
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data
saved on the operator.
All Modes
0: Read operation prohibited
1: Read operation allowed
Description
1.3 Parameter Table
Setting
Default:
<36>
common_
Min: 1
Max: 60000
Default:
<36>
Min: 0
Max: 3
common_
Default: 1
Min: 0
Max: 1
Default: 1
common_
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 2
Default:
Determined by
common_
drive capacity
Min: –
Max: –
common_
Default: 0
Min: 0
Max: 1
Default: 0
common_
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
Do not change this
setting.
Min: –
Max: –
Default:
<6>
common_
Min: 0 V
Max: 20000 V
common_
Default: 0
Min: 0
Max: 3
Default: 0
common_
Min: 0
Max: 1
Page
222
222
222
223
223
224
224
224
224
225
225
225
67