Profibus-Dp Parameters; Devicenet Parameters - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

F6-06: Torque Reference / Torque Limit Selection from Comm. Option
Used to select if torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06
Torque Reference / Torque Limit Selection from Comm. Option
Setting 0: Enabled
Setting 1: Disabled
F6-07: Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Selects how multi-step speed inputs are treated when the NetRef command is set.
No.
F6-07
Setting 0: Multi-step speed operation disabled
If the NetRef command is selected, multi-step speed input frequency references are disabled.
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option.
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-
A1-03.
No.
F6-08
Setting 0: Do not reset parameters F6-
Setting 1: Reset F6-
Note: F6-08 is not reset when the drive is initialized.

◆ PROFIBUS-DP Parameters

Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card PROFIBUS-DP Installation Manual
and Technical Manual.

◆ DeviceNet Parameters

Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the YASKAWA AC Drive-Option Card DeviceNet Installation Manual and
Technical Manual.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
Parameter Name
Parameter Name
NetRef/ComRef Function Selection
Parameter Name
Reset Communication Parameters
when the drive is initialized with A1-03
when the drive is initialized with A1-03
Setting Range
0, 1
Setting Range
0, 1
) are reset when the drive is initialized using parameter
Setting Range
0, 1
2.6 F: Option Settings
Default
0
Default
0
Default
0
165

Advertisement

Table of Contents
loading

Table of Contents