YASKAWA FSDrive-MV1000 Parameter Manual page 31

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

No.
Name
(Addr.)
C5-23
Motor 2 ASR
(358H)
Proportional Gain 2 Sets the speed control gain 2 of the speed control loop (ASR) for motor 2.
C5-24
Motor 2 ASR
(359H)
Integral Time 2
Motor 2 ASR
C5-26
Primary Delay
(35BH)
Time Constant
Motor 2 ASR Gain
C5-27
Switching
(35CH)
Frequency
C5-28
Motor 2 ASR
(35DH)
Integral Limit
<10> Default setting is determined by the control mode (A1-02).
<12> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if
the accel/decel time setting units are set to 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
<15> The default setting is determined according to the control mode for motor 2 (E3-01).
<16> Default setting is determined by the control mode (A1-02) and the drive model (o2-04).
<17> The setting range is 1.00 to 300.0 in CLV.
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
V/f
OLV
V/f
OLV
Sets the integral time 2 of the speed control loop (ASR) for motor 2.
V/f
OLV
Sets the filter time constant for the time from the speed loop to the torque
command output used for motor 2.
V/f
OLV
Sets the frequency for switching between proportional gain 1, 2 and
integral time 1, 2.
V/f
OLV
Sets the ASR integral upper limit for motor 2 as a percentage of rated load
torque.
Description
CLV
CLV
CLV
CLV
CLV
1.3 Parameter Table
Setting
Default:
<15>
Min: 0.00
common
Max: 300.00
<17>
Default:
<15>
Min: 0.000 s
common
Max: 10.000 s
Default:
<15>
common
Min: 0.000 s
Max: 0.500 s
Default: 0.0 Hz
common
Min: 0.0 Hz
Max: 120.0 Hz
Default: 200%
common
Min: 0%
Max: 400%
page
134
134
134
134
134
31