1. Conformance to international standards
Composition of Peripheral Equipments
Surge Absorber
Option part No.
DV0P1450
DV0P4190
Remarks
When performing withstand voltage test of machine and equipment, be sure to remove the
surge absorber; otherwise, it will be damaged.
Residual current device
Install a residual current device (RCD) at primary side of the power supply.
Select a RCD of type.B prescribed in IEC60947-2, JISC8201-2-2
Grounding
(1) To prevent electric shock, be sure to connect the ground terminal (
and the ground terminal (PE) of the control panel.
(2) The ground terminal (
minals are provided.
Note
For driver and applicable peripheral equipments, refer to P.2-10 "Driver and List of Applicable
Peripheral Equipments".
Related page
• P.7-108 "Options"