1-Button Light Scene Extension Unit With Memory Function - Light Scene Number; 1-Button Operating Mode "Adjust Rtc" - Enable; 1-Button Operating Mode "Adjust Rtc" - Operating Mode; 1-Button Operating Mode "Adjust Rtc" - Operating Mode Comfort - ABB ClimaECO SBS/Ux.0.1 Series Product Manual

Table of Contents

Advertisement

12.1.104 1-button light scene extension unit with memory function - Light scene number

Name
Sx: Light scene number:
At a normal press of the button the light scene number is sent on the bus via the 1-byte
communication object.
At a long press of the button a memory bit is sent in addition to the light scene number.
12.1.105 1-button operating mode "Adjust RTC" — Enable
Name
Sx: Enable
The RTC function can be temporarily blocked or enabled via the 1-bit communication object.
12.1.106 1-button operating mode "Adjust RTC" — Operating mode
Name
Sx: Operating mode
The value for the switchover of operating mode is sent via the 1-byte communication object.
Meaning of values:
"0": Auto
"1": Comfort
"2": Standby
"3": Night
"4": Frost/heat protection
12.1.107 1-button operating mode "Adjust RTC" — Operating mode comfort
Name
Sx: Operating mode comfort
The comfort operating mode is sent to the bus via the 1-bit communication object. The telegram
that is sent, always has the inverted value of the value sent last. This means that "0" or "1" is
sent (toggle mode) alternately via the object at each press of the button.
Product manual 2CKA001473B9679
Object function
Output
Object function
Input
Object function
Output
Object function
Output
Communication objects
Communication objects
Data type
18.001 Scenes
Control
Data type
1.001 Switching
Data type
20.102 HVAC mode
Data type
1.001 Switching