Assembly; Figure 7: Masterlink Communication Cable (For Boards With Part Number 2104836-001); Figure 8: Masterlink Communication Cable (For Boards With Part Number 2018546-005) - ABB LevelMaster 7100 User Manual

Liquid level sensor with batteryless float support
Hide thumbs Also See for LevelMaster 7100:
Table of Contents

Advertisement

Figure 7 shows the cable converter and adapter required for connection to board part number 2104836-001.

Figure 7: MasterLink communication cable (for boards with part number 2104836-001)

CAUTION – Equipment damage. The RS-485-to-RS-232 converter cables have 1 or 2 batteries (9 Vdc) which
supply power to the boards during direct connection. No additional voltage source is required during direct
connection for configuration.
Do not use two batteries to supply power to boards with part number 2104836-001. The boards will be damaged
when the supplied power is greater than 15 Vdc (2 fully charged 9 Vdc batteries can supply up to 18 Vdc).
To prevent battery drain when converter cables are not in use, make sure the red wire is removed from the
positive terminal contact on the battery holder.
Figure 8 shows the cable converter and adapter required for connection to board part number 2018546-005.
RS-232/RS-485 converter
P/N 2100241-002
Connect to Computer
1. Serial or
2. USB (using additional adapter )

Figure 8: MasterLink communication cable (for boards with part number 2018546-005)

Assembly

The cord connector, tank port bushing, floats and float clamp are not typically installed on the LevelMaster for shipping. Follow
this procedure to install these components after verifying all parts have been received and while the unit is lying on wooden
blocks on the ground. It is assumed that the LevelMaster is being installed through a standard 3 inch or 4 inch tank port opening.
Tools and materials required:
24 inch pipe wrench
Phillips screwdriver
®
Teflon
tape
2 wooden blocks to support the unit
To assemble components on the LevelMaster before insertion into the tank:
Note: Disconnect the red wire connector from battery
holder when cable is not in use . Failure to do so will result
in a constant battery drain .
9V Batt
+
9V Batt
Cable Adapter
P/N 2100250 -001
Connect to Level Master board
P/N 2018546 -005
LevelMaster 7100 User manual 2105835 Rev AA | 15

Advertisement

Table of Contents
loading

Table of Contents