12.1.42 RTC - Summer compensation active
Name
RTC: Summer compensation
active
The controller uses this 1-bit communication object to send a switching signal to the bus. If
summer compensation is active, value "1" is sent. If summer compensation is not active, value
"0" is sent.
If summer compensation is active, the set setpoint temperature for cooling operation is raised in
dependence of the outside temperature. A decrease of the cooling mode setpoint temperature
below the value calculated by the summer compensation function is not possible. An increase of
the setpoint temperature for the cooling mode is always possible.

12.1.43 RTC - Temperature calibration

Name
RTC: Temperature calibration
The temperature measured locally in the device can be calibrated via the 2-byte temperature
value. It can be set whether the calibration is performed as new temperature value or as
differential value to the currently measured temperature.

12.1.44 RTC - On/off request

Name
RTC: On/off request (master)
RTC: On/off request (slave)
The 1-bit switching object is used to transmit the switch-on/off request of the button operation of
a slave device to the master device. The confirmation is made via object "Control On/Off".
Notice
When the master/slave operation is activated, the object "RTC: On/Off request
(master)" of the master device for synchronisation must be connected with
object "RTC: On/Off request (slave)" of the slave device.
Product manual 2CKA001473B9679
Object function
Output
Object function
Input
Object function
Input
Output
Communication objects
Communication objects
Data type
1.001 Switching
Data type
9.001 Temperature value
9.002 Differential temperature value
Data type
1.001 Switching
1.001 Switching